Automated Day Tanks Systems and Automated Generator Base Tank Systems
Closed Top Diked
This is E&CA's standard Generator Base Tank. The tank is of a single wall construction, and the rails have been designed to support the weight of the generator set. Each gusseted bolt hole has been designed and tested to support up to 4000 lbs. If this tank is UL Listed, it will include an emergency vent connection. This connection can be fitted with an optional back pressure relief valve set at 8 oz. A tank which is to meet NFPA-30 of the National Fire Protection Association requires that the tank be built to "Recognized Standards of Design". E&CA has elected to use UL-142, 1995 as its standard.
Heavy gauge steel construction 10 gauge steel top, bottom, and ends
7 gauge steel channel sides
12 gauge steel baffles
1 1/2" NPT level gauge
2" fill connection
1 1/4" NPT normal vent connection inner tank
1" NPT fuel return
1" NPT Level Switch connection
1" x 1/2" NPT removable fuel supply dip tube 3/8" NPT exterior drain
No fixed heights (recommended maximum 36")
Each tank designed to your specifications
Tank baffles to increase structural strength and to cool fuel
Inner tank pressure tested to 3 psi
Four sided complete base enclosure
Interior - rust proofing epoxy coated
Exterior - E&CA gray enamel or optional gloss black
Home | Day Tanks | Generator Base Tanks | Meter Panels | Enclosures| Pump Sets | Literature | Local Reps | Site Map | Contact Us